Fire Alarm Control Panel 4 ZONE, 8 ZONE

Fire Alarm Control Panel 4 ZONE, 8 ZONE

Features

Zone and Display
Each Zone is represented by three LED, one Red and two Orange color.
FIRE (Red LED): Fire Alarm Signal
O/C FAULT (Orange LED): Open Circuit
S/C FAULT (Orange LED): Short Circuit 

Sounder Circuits

  1. Two external sounder output circuits are provided.
  2. Amount of two sounder outputs is 150mA.
  3. Each sounder circuit is protected by fuse (1A).
  4. Each sounder circuit should be with End of Line Resistance (10KΩ) to check if open circuit or short circuit.
  5. Press EVACUATE button can re-sound the external alarm (alarm bell, buzzer).
  6. Press the SILENCE button to mute the external sounders (alarm bell, buzzer).

Circuit Connection Diagram 

Specification

Mains Supply 220V AC 50/60 Hz
Spare Power (Battery) 24V DC
Charging Voltage Protection Glass Fuse
Sounder Output 24V DC (End of Line Resistance 10KΩ)
Max. Output Current: 150mA amount
Amount of Smoke Detectors Max. Amount of Connection: 20 / Loop
Auxiliary Contacts Null-Voltage Contact (24VDC, 1A max. NO/NC)
Mains Supply Protection Glass Fuse
Sounder Protection Glass Fuse
Spare Power (Battery) Protection Glass Fuse
Zone End of Line Resistance 5.1KΩ

Fire Alarm Control Panel 5 ZONE, 10 ZONE

Fire Alarm Control Panel 5 ZONE, 10 ZONE

Fire Alarm Control Panel 5 ZONE, 10 ZONE

Features

  • Alarm Verification: To avoid false alarm from environment interference and unstable pulse. On receiving a fire signal from detector or manual call point, Panel accumulates the fire signal before Alarm Verification time: 12 seconds, if the fire signal is still existing, Panel start to alert.
  • Zone test: Alarm and Fault function test.
  • Back up battery test.
  • Fault indications for wire disconnection, unstable AC power, battery short circuit or disconnection and fuse trouble.
  • Different sounds to indicate fire alarm or disconnection.
  • Annunciator is available to connect with.

Specification

Model HC-5AL HC-10AL
Total Loops 5 Loops 10 Loops
Input Power 220VAC 50/60Hz
Aux. Power (Spare Battery) DC 24V 300mAH (NI-Cd Battery) DC 24V 600mAH (NI-Cd Battery)
Charging Voltage/Current DC 29V 60mA
Loop Valtage, Current Nomal: DC24V, Short-Circuit: 5V, Under 30mA
Exterio Resistance Round-trip under50Ω
Amount of Smoke Detectors Max. Amount of Connection: 20/ Loop
Amount of Heat Detectors No Limit (Except Electronic Type)
End of Line Resistance 10KΩ
Output Current for Indicating Lamp Max. Output Current: 120mA Max. Output Current: 240mA
Output Current for Alam Bell Max. Output Current: 120mA Max. Output Current: 240mA
Case Material ABS resin with non-flammability
Auxiliary Contact 1 Null-Valtage Contact (N/O, 250VAC, 7A)

Fire Alarm Control Panel 5~100+ ZONE

Fire Alarm Control Panel 5~100+ ZONE

Fire Alarm Control Panel 5~100+ ZONE

Description

The panel system is microcomputer designed for fire alarm, smoke exhaust, water sprinkle, fire-fighting foam control. All PCB are based on modules and stable, easy replace and maintain. Auto test function makes it easy to check and control.

Features

  1. Alarm Verification: 
    Double check the fire alarm signal if is real to avoid false alarm. When receiving a fire alarm signal, panel will wait for 5~8 seconds before transmitting fire alarm. If panel receive a fire alarm signal at first time and receive the same signal again within 5~8 seconds, it will transmit. If not receive a fire alarm signal again within 5~8 seconds, it will cancel.
  2. Battery self-protect:
    If AC power cut, it will transfer automatically to use battery power. When battery is running lower 18VDC, it will stop discharging to avoid over discharge. 
  3. Indication LED: 
    Different color light to indicate different condition. 
    Green light: AC power normal. 
    Yellow and Red light: abnormal condition with alarm sound.
  4. Circuit auto and manual test: Test circuit from 1 to last automatically or set a certain circuit manually to test. 
  5. Annunciator Panel is available.

Electric Specification

Type Conventional type Spare Battery 24VDC
Model HC-5AL..HC-100L End of Line Resistance 10KΩ
Zone 5~100+ Max. Amount of smoke detectors 20 pcs/Loop
Input Voltage 220VAC/50Hz Alarm Verifying Time 7 seconds
Operation Voltage 24VDC Exterior Resistance Round-trip under 56Ω


Size 

5~15 zone 20~30 zone 35~60 zone 66~90 zone 95~100 zone
300(W)
410(H)
107(D)
mm
370(W)
510(H)
150(D)
mm
480(W)
720(H)
200(D) 
mm
480(W)
850(H)
200(D)
mm
480(W)
1000(H)
220(D)
mm

Fire Alarm Control Panel

Berbagai macam merk dan jenis dari Fire Alarm Control Panel yang beredar di indonesia, akan tetapi masing-masing memiliki kelebihan dan kekurangannya. Kami sebagai distributor dari berbagai merk fire alarm control panel menyediakan stok yang tersedia untuk mempermudah para pemain jasa instalasi fire alarm di indonesia.

PT. Amare Aqila Indonesia sudah sangat berpengalaman dalam menyediakan perlengkapan fire alarm dan menyediakan pemasangan atau instalasi fire alarm baik konvensional maupun addressable.

Segera dapatkan Harga yang menarik dari kami, hubungi :

Tlp. 021 7463 9917 (hunting)
Fax. 021 7463 9918
Hp (Devi). 0858 8225 9931 (WA/LINE)
Hp (Tasya). 0856 7549 032 (WA/LINE)
Email. sales@amare.co.id

Klik >> Donwload Browsur Fire Alarm Control Panel Hong Chang